When it comes to firefighting in high-rise buildings, the use of Oblique Hydrant Valves becomes paramount. These valves are specially designed to ensure uniform firefighting pressure at all levels of the building, even in varying storeys. They are manufactured to conform to BS 5041 standards, ensuring their quality and reliability.
Valves is their ability to maintain pressure control despite the difference in inlet pressures that may occur at different levels of the building. This means that firefighters can rely on these valves to provide the appropriate pressure needed to fight fires, no matter where they are in the building.
The Oblique Hydrant Valve is classified under low pressure, making it suitable for use at nominal inlet pressures up to 15 bar. This low-pressure classification ensures that the valve is safe to use and prevents any risk of over-pressurization.
The body of the valve is made of high-quality copper alloy, which provides excellent strength and durability. The use of copper alloy also ensures that the valve is corrosion-resistant and can withstand harsh environments. The valve has a blank cap made of copper alloy, plastic, or aluminum that can be easily replaced if needed.
One of the unique features of the Oblique Hydrant Valve is its ability to replace the gland seal while under pressure and with the valve fully closed. This has important safety implications when working with pressurized water systems, as it reduces the risk of leaks or other problems that could cause water damage or other issues.
2.Product Parameter
|
Code No. |
XH001-006C-00 |
|
Body Material |
Copper Alloy |
|
Inlet |
2.5"BSP male thread |
|
Outlet |
2.5"BS 336 Female coupling with plastic cap & chain |
|
Test pressure |
Valve Seat Test at 16.5 Bar • Body Test at 22.5 Bar |
|
Water Flow Rate |
8.5 L/S @ 4 Bar Outlet Pressure |