Pre-installation Preparation
Equipment Inspection
Before installation, a comprehensive inspection of the ultrafine dry powder fire extinguisher and its related components should be conducted, including but not limited to:
Whether the model, specifications, and quantity of the fire extinguisher meet the design requirements;
Whether the nameplates of each component are clear and without missing text;
Whether the appearance is intact and free from rust, deformation, or other problems;
Whether the filling pressure in the gas cylinder meets the design requirements;
Whether the working pressure value of the pressure controller on the powder tank meets the design requirements (usually 1.6 MPa).
Installation Location Selection
Fire extinguishing devices should be installed in locations convenient for construction, maintenance, and dismantling, and should not obstruct normal logistics operations;
They should be avoided from lighting fixtures, air conditioning ducts, and other facilities that may impede the normal operation of the fire extinguishing device;
Suspended ultra-fine dry powder fire extinguishers should be installed 1.5 to 2.5 meters above the ground to ensure rapid activation and a wider coverage area;
The installation location should avoid areas exposed to rain, flooding, and frequent vibration, impact, or corrosion.
Installation Steps
Suspended Installation
1. Fixed Bracket Installation:
Use two expansion bolts (M10) to secure the fixed bracket to the precast concrete slab above the protected area, ensuring the bracket is stable and not loose.
Screw the upper lifting ring of the fire extinguishing device into the threaded rod (M12) below the fixed plate to a depth of not less than 15mm.
2. Fire Extinguishing Device Hanging:
Connect the fire extinguishing device to the fixed bracket via the lifting ring, ensuring a secure and reliable connection.
The activation module can be installed on the fixed bracket or directly hung on the nearest wall or ceiling.
Wall-Mounted Installation
If wall-mounted installation is used, use expansion bolts to fix the mounting plate to the wall, then connect and tighten the fire extinguishing device to the mounting plate using bolts.
Ensure there are no obstructions within 1.0m directly in front of the main exhaust port of the fire extinguishing device, and within 0.2m behind, to the sides, and above the device.
Fire Extinguishing System Linkage Control
Fire Alarm System Linkage
The ultrafine dry powder fire extinguishing system should be linked to the fire alarm system to achieve automatic detection and alarm of fire signals.
After a 30-second delay, the alarm system sends an activation signal to the fire extinguishing system. Upon receiving the signal, the fire extinguishing system activates the extinguishing agent.
Emergency Start and Stop
In manned protected areas, an emergency start button can be installed to manually activate the fire extinguishing system after fire confirmation.
An emergency stop button is used to stop the fire extinguishing system in special circumstances, but it should be noted that the emergency stop time is limited (usually 30 seconds).
Installation Precautions
1. During Installation:
Do not connect to power during installation to prevent accidental activation;
Wrap wire joints with high-quality insulating tape to ensure no short circuits;
When installing and debugging the system, manual switches should be in the off position, and the connection to the fireproof power supply should be verified beforehand.
2. Distance between Fire Extinguishing Devices and Live Equipment:
The minimum distance between fire extinguishing devices and their components and live equipment should not be less than 0.2m, and the casing should be grounded.
3. Piping and Wiring Requirements:
The installation of steel pipes and metal slots should meet design requirements, ensuring that the conduit is free of wrinkles, dents, and cracks;
The bending radius should meet the specifications to ensure smooth and unobstructed wiring.
Maintenance and Care
The fire extinguishing system should be placed in a dry, well-ventilated area, protected from direct sunlight, rain, or contact with corrosive substances;
Regularly check the working status of key components of the fire extinguishing system, such as the pressure controller and electromagnetic start valve;
Ensure sufficient backup power. If the external power supply is interrupted for more than 24 hours, the backup battery should be charged promptly.
Conclusion
The correct installation of ultrafine dry powder fire extinguishers is crucial for ensuring fire safety. By following the installation guidelines described in this article, it can be ensured that the fire extinguishing device can function promptly and effectively in the event of a fire, reducing fire losses and protecting the safety of people and property.